Electrical installation

Important notes

6

EN

28

Lenze ¯ BA 33.0006 ¯ 3.0

6

Electrical installation

6.1

Important notes

{

Danger!

Hazardous voltage on the power connections even when disconnected
from mains: residual voltage >60 V!
Before working on the power connections, always disconnect the drive
component from the mains and wait until the motor is at standstill.
Verify safe isolation from supply!

(

Stop!

Electrical connections must be carried out in accordance with the
national and regional regulations!

Observe tolerances according to IEC/EN 60034−1:

–

Voltage ±5 %

–

Frequency ±2 %

–

Wave form, symmetry (increases heating and affects electromagnetic
compatibility)

Observe notes on wiring, information on the nameplate, and the connection scheme in
the terminal box.

¯

The connection must ensure a continuous and safe electrical supply, i.e.

–

no loose wire ends,

–

use assigned cable end fittings,

–

ensure good electrical conductivity of the contact (remove residual lacquer) if an
(additional) PE connection on the motor housing is used),

–

establish a safe PE conductor connection,

–

tighten the plugin connector to the limit stop.

–

After the connection is completed, make sure that all connections on the
terminal board are firmly tightened.

¯

The smallest air gaps between uncoated, live parts and against earth must not fall
below the following values.

Minimum requirements for basic
insulation according to IEC/EN
60664−1 (CE)

Higher requirements for UL
design

Motor diameter

3.87 mm

6.4 mm

< 178 mm

9.5 mm

> 178 mm

¯

The terminal box has to be free of foreign bodies, dirt, and humidity.

¯

All unused cable entries and the box itself must be sealed against dust and water.