5 i/o, 2 rs485 and modbus, 3 can – Lenze IM94MV01C User Manual

Page 18: 1 digital i/o

Advertising
background image

16

IM94MV01C

2.4.2 RS485 and Modbus

The [RS485 and Modbus] folder contains the configuration parameters of the Modbus interface. Click on any Modbus parameter
to change it. Table 4 lists the range and default value of each RS485 Modbus parameter.

Table 4: RS 485 Modbus Parameters

Parameter

Range

Default Value

RS 485 Configuration

Normal, Modbus slave

Normal

Modbus baud rate

400, 4800, 9600, 1900, 38400, 57600, 11500

1900

Modbus reply delay

0 - 1000ms

0

Modbus parity

No Parity, Odd, Even

No Parity

Modbus stop bits

1.0, 1.5, .0

1.0

2.4.3 CAN

The [CAN] folder contains the configuration parameters for the CAN interface. Click on Parameter name to change the setting
of that parameter. Table 5 lists the range and default value for each CAN parameter.

Table 5: CAN Parameters

Parameter

Range

Default Value

CAN Control

Disabled, CANOpen Simple, CANOpen 40

Disabled

CAN baud rate

10k, 5k, 50k, 15k, 50k, 500k, 800k, 1000k

500k

CAN Address

1 - 17

1

CAN Bootup Mode

Pre-operational, Operational, Pseudo master mode

Pre-operational

CAN Bootup Delay

0-5 sec

5 sec

2.5 I/O

There are  sub-folders under the [I/O] folder in the MotionView Node Tree. The [Digital I/O] folder contains the values of the 4
outputs and debounce times for the 1 inputs. The [Analog I/O] folder contains the values of the one output and one input plus
an action button [Adjust analog input zero offset] that permits the user to change the analog zero offset.

2.5.1 Digital I/O

The [Digital I/O] folder contains the values of the 4 outputs and debounce times for the 1 inputs (A1-A4, B1-B4, C1-C4).

Table 6: Digital Input/Output Parameters

Parameter

Range

Default Value

Output 1 function

Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position

Not assigned

Output  function

Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position

Not assigned

Output 3 function

Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position

Not assigned

Output 4 function

Not assigned, Zero Speed, In speed window, Current
limit, Run time fault, Ready, Brake, In position

Not assigned

Input A1 debounce time

0-1000 ms

0

Input A debounce time

0-1000 ms

0

Input A3 debounce time

0-1000 ms

0

Input A4 debounce time

0-1000 ms

0

Input B1 debounce time

0-1000 ms

0

Input B debounce time

0-1000 ms

0

Input B3 debounce time

0-1000 ms

0

Input B4 debounce time

0-1000 ms

0

Input C1 debounce time

0-1000 ms

0

Input C debounce time

0-1000 ms

0

Input C3 debounce time

0-1000 ms

0

Input C4 debounce time

0-1000 ms

0

Hard limit switches action

Not assigned, Fault, Stop and fault

Not assigned