RG-MHMOD 6

Drive Setup & Operation

4

MCH Drive Setup & Operation

4.1 Serial Address

All AC Tech drives have a Serial Address Parameter that must be programmed prior to attempting to
operate the serial interface (Programming Parameter #58 / AC Tech Register #109).

4.2 Serial Communications Parameter

All AC Tech drives have a Serial Communications Parameter that governs the operation of the Serial Link.
On MCH drives this is #57 SERIAL LINK (register #108). Table 4 lists the selections for MCH Parameter 57,
SERIAL LINK.

Table 4: MCH Parameter 57 Selections

Setting

Description

Watchdog Timeout Period

00

DISABLE

01

WITH TIMER

10 sec

02

WITHOUT TIMER

Explanation of Terms:

• DISABLED

serial link not operational (this is the drive's default setting)

• WITH TIMER

serial link allows reading & writing of both control & programming parameters.
Watchdog timer is enabled (refer to section 4.6,

Watchdog Timer

).

• WITHOUT TIMER serial link allows reading & writing of both control & programming parameters.

Watchdog timer is disabled (refer to section 4.6,

Watchdog Timer

).

Prior to attempting to communicate with the drive, Serial Communications Parameter must be appropriately
programmed.

4.3 Control Parameter

The Control Parameter on MCH drives (Programming Parameter #30 / AC Tech Register #81) determines
how much control a user has over a drive via the serial link. The Control Parameter must be appropriately
programmed for a particular application. Refer to the MCH Series Installation and Operation Manual (MH01)
for a detailed explanation on programming the drive parameters.

Table 5: Control (Parameter 30)

Setting

Description

00

NORMAL (default)

01

NORM NO HAND

02

SERIAL SPEED

03

S SPD / NO HAND

04

SERIAL AUTO

05

S AUTO / NO HAND