Drive Control & Communication

NOTE 4 - Acceleration Limits

Acceleration Limits

HP

Adjustment Range

0.25 - 20

1 - 36000 (0.1 - 3600 sec)

25 - 60

3 - 36000 (0.3 - 3600 sec)

75 - 250

6 - 36000 (0.6 - 3600 sec)

NOTE 5 - Deceleration Limits

Deceleration Limits

HP

Adjustment Range

240/200 VAC

480/400 VAC

590/480 VAC

without dB

with dB

0.25 - 7.5

1 - 7.5

3 - 36000 (0.3 - 3600 sec)

1 - 36000 (0.1 - 3600 sec)

10 - 15

10 - 20

1 - 7.5

5 - 36000 (0.5 - 3600 sec)

1 - 36000 (0.1 - 3600 sec)

20 - 30

25 - 60

10 - 20

10 - 36000 (1.0 - 3600 sec)

2 - 36000 (0.2 - 3600 sec)

25 - 60

20 - 36000 (2.0 - 3600 sec)

2 - 36000 (0.2 - 3600 sec)

NOTE 6 - MAX DC BRAKE VOLTAGE (Register 63)

Maximum DC Brake Voltage

Model

MH100

MH200

MH400

MH500

Voltage

240/120 Vac

240/200 Vac

480/400 Vac

590/480 Vac

MAX Brake Voltage

24 V

24 V

48 V

59 V

NOTE 7 - CURRENT (Register 67)

If LINE VOLTS, Register 51, is set to LOW (or set to Auto and the input voltage is low), the range for
CURRENT is 25 - 150%.

NOTE 8 - FX BOOST (Register 70)

FX BOOST Factory Default Setting

HP

Factory Default

HP

Factory Default

0.25 - 1

5.30%

15

2.20%

1.5 - 2

4.40%

20

2.00%

3

3.60%

25

1.80%

5

3.00%

30

1.60%

7.5

2.70%

40

1.20%

10

2.40%

50 - 60

0.80%