Drive control & communication, 2 parameter list – Lenze MCH Series Drives Modbus Communications User Manual

Page 25

Advertising
background image

21 RG-MHMOD

Drive Control & Communication

6.2 Parameter List

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

51 (33)

0

LINE VOLTS

00 - High
01 - Low
02 - Auto

02 - Auto

52 (34)

1

SPEED #1

Min. Frequency - Max. Frequency

2000 (20.00 Hz)

2

53 (35)

2

SPEED #2

Min. Frequency - Max. Frequency

2000 (20.00 Hz)

2

54 (36)

3

SPEED #3

Min. Frequency - Max. Frequency

2000 (20.00 Hz)

2

55 (37)

4

SPEED #4

Min. Frequency - Max. Frequency

2000 (20.00 Hz)

2

56 (38)

5

SKIP #1

.00 Hz - Max. Frequency

00 (.00 Hz)

2

57 (39)

6

SKIP #1

.00 Hz - Max. Frequency

00 (.00 Hz)

2

58 (3A)

7

BAND WID

0 - 1000 (.00 - 10.00 Hz)

100 (1.00 Hz)

2

59 (3B)

8

ACCEL

Refer to Note 4

300 (30.0 sec)

60 (3C)

9

DECEL

Refer to Note 5

300 (30.0 sec)

61 (3D)

10

MIN FREQ

.00 - Max Frequency

50 (.50 Hz)

2

62 (3E)

11

MAX FREQ

Min Frequency - 12000 (120.00 Hz)

6000 (60.00 Hz)

2

63 (3F)

12

DC BRAKE

Refer to Note 6

0 (.0 VDC)

64 (40)

13

DC TIME

0 - 9999 (.0 - 999.9 sec)

0 (.0 sec)

65 (41)

14

DYN BRAKE

00 - Off
01 - On

00 - Off

67 (43)

16

CURRENT

25 - 180 (25 - 180%), Refer to Note 7

180 (180%)

68 (44)

17

MOTOR OL

25 - 100 (25 - 100%)

100 (100%)

69 (45)

18

BASE

2000 - 36000 (20.00 - 360.0 Hz)

6000 (60.00 Hz)

2

70 (46)

19

FX BOOST

0 - 300 (.0 - 30.0%), Refer to Note 8

73 (49)

22

TORQUE

00 - Contant
01 - Variable
02 - CT/NOCMP

00 - Constant

74 (4A)

23

CARRIER

00 - 2.5 kHz
01 - 6 kHz
02 - 8 kHz
03 - 10 kHz
04 - 12 kHz
05 - 14 kHz

00 - 2.5 kHz

76 (4C)

25

START

00 - Normal
01 - Power-Up
02 - Auto 1
03 - Auto 2
04 - Auto 3

00 - Normal