23 RG-MHMOD

Drive Control & Communication

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

95 (5F)

44

TB10B OUT

00 - None
01 - 0 - 10 VDC
02 - 2 - 10 VDC

00 - None

96 (60)

45

@TB10B

10 - 200 (10 - 200%)

125 (125%)

98 (62)

47

TB13A

00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #1
04 - DEC FREQ
05 - REVERSE

00 - None

99 (63)

48

TB13B

00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #2
04 - INC FREQ

00 - None

100 (64)

49

TB13C

00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #3
04 - HAND
05 - REVERSE

00 - None

101 (65)

50

TB13D

00 - EXT Fault
01 - EXT /Fault
02 - EXT Clear

00 - EXT Fault

103 (67)
104 (68)
105 (69)

52
53
54

TB14OUT
TB15OUT
RELAY

00 - None
01 - Run
02 - Fault
03 - INV Fault
04 - Fault Lockout
05 - @ Speed
06 - Above Preset #3
07 - Current Limit
08 - AUTO/HAND SRC
09 - FLWR PRESET
10 - MIN/MAX ALARM

11 - INV MIN/MAX ALM
12 - MIN ALARM
13 - INV MIN ALARM
14 - MAX ALARM
15 - INV MAX ALARM
16 - RUN REVERSE

00 - None

106 (6A)

55

TB5B LOSS

00 - Fault
01 - Preset #3

00 - Fault

108 (6C)

57

SERIAL

00 - Disable
01 - w/ Timer
02 - w/o Timer

00 - Disable

109 (6D)

58

ADDRESS

1 - 247

30

112 (70)

61

PASSWORD

0000 - 9999

0019

114 (72)

63

SOFTWARE

(View Only)

(N/A)

1

= Drive's programming parameter number;

2

= Two decimal places assumed (hundredths)