Drive control & communication – Lenze MCH Series Drives Modbus Communications User Manual

Page 28

Advertising
background image

RG-MHMOD 24

Drive Control & Communication

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

115 (73)

64

MONITOR

00 - OFF
01 - ON

01 - ON

116 (74)

65

PROGRAM

00 - Maintain
01 - Reset 60
02 - Reset 50

01 - Reset 60

117 (75)

66

HISTORY

00 - Maintain
01 - Clear

00 - Maintain

121 (79)

70

PID MODE

00 - Off
01 - Normal
02 - Reverse

00 - Off

125 (7D)

74

PID FB

00 - TB-5A
01 - TB-5B

00 - TB-5A

126 (7E)

75

FB @ MIN

0 - 65000

0 (0.0%)

127 (7F)

76

FB @ MAX

0 - 65000

65000 (100%)

128 (80)

77

P GAIN

0 - 9999 (0.0 - 999.9%)

50 (5.0%)

129 (81)

78

I GAIN

0 - 100 (0.0 - 10.0 sec)

0 (0.0 sec)

130 (82)

79

D GAIN

0 - 100 (0.0 - 10.0 sec)

0 (0.0 sec)

131 (83)

80

PID ACC

0 - 1000 (0.0 - 100.0 sec)

300 (30.0 sec)

132 (84)

81

MIN ALRM

FB @ MIN - FB @ MAX

0.0%

133 (85)

82

MAX ALRM

FB @ MIN - FB @ MAX

0.0%

149 (95)

98

LANGUAGE

English

150 (96)

99

FAULT HISTORY

(View Only)

(N/A)

1

= Drive's programming parameter number;

2

= Two decimal places assumed (hundredths)