Drive control & communication – Lenze MCH Series Drives Modbus Communications User Manual

Page 26

Advertising
background image

RG-MHMOD 22

Drive Control & Communication

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

77 (4D)

26

STOP

00 - Ramp
01 - Coast

00 - Coast

79 (4F)

28

SPEED SRC KEY

00 - Enabled
01 - Disabled

00 - Enabled

80 (50)

29

HAND SRC

00 - Keypad
01 - 0-10 VDC
02 - 4-20mA
03 - Preset #1
04 - Preset #2
05 - Preset #3
06 - Preset #4
07 - MOP
08 - Selected

00 - Keypad

81 (51)

30

CONTROL

00 - Normal
01 - Normal / No Hand
02 - Serial Speed
03 - Serial Speed / No Hand
04 - Serial Auto
05 - Serial Auto / No Hand

00 - Normal

82 (52)

31

UNITS

00 - Hertz
01 - RPM
02 - % Hz
03 - /SEC
04 - /MIN
05 - /HR
06 - None

07 - %
08 - PSI
09 - FPM
10 - CFM
11 - GPM
12 - IN
13 - FT

14 - /SEC
15 - /MIN
16 - /HR
17 - F
18 - C
19 - MPM

00 - Hertz

83 (53)

32

HZ MULT

10 - 65000 (.10 - 650.00)

100 (1.00)

2

84 (54)

33

UNITS DP

00 - XXXXX
01 - XXX.X
02 - XX.XX
03 - X.XXX
04 - .XXXX

00 - XXXXX

85 (55)

34

LOAD MLT

95 - 139 (95 - 139%)

100 (100%)

86 (56)

35

CONTRAST

00 - Low
01 - Medium
02 - High

02 - High

90 (5A)

39

TB5 MIN

0 - 36000 (.00 - 360.00 Hz)

0 (.00 Hz)

2

91 (5B)

40

TB5 MAX

0 - 36000 (.00 - 360.00 Hz)

0 (.00 Hz)

2

93 (5D)

42

TB10A OUT

00 - None
01 - 0 - 10 VDC
02 - 2 - 10 VDC

00 - None

94 (5E)

43

@TB10A

300 - 36000 (3.00 - 360.00 Hz)

6000 (60.00 Hz)

2

1

= Drive's programming parameter number;

2

= Two decimal places assumed (hundredths)

Advertising