Alarm indications – RKI Instruments Beacon 110 User Manual

Page 26

Advertising
background image

22

Beacon 110 Operator’s Manual

Alarm Indications

NOTE:

The Beacon 110 includes alarm on and alarm off delay settings for alarm 1 and
alarm 2. The alarm indications described in this section operate according to
the factory set alarm settings. See Table 7 on page 27 for all the factory
settings.

NOTE:

You can select normally energized (N. EN) or normally de-energized (N. DE-
EN) alarm 1 and alarm 2 relay settings in Configuration Mode. The following
sections describe the standard factory setting for these relays which is
N. DE-EN.

The fail relay is set as normally energized in the firmware and is not user-
adjustable.

Table 6: Visual and Audible Alarm Indications

Condition

Cause

Visual Indication(s)

Audible

Indication

Alarm 1

1

Increasing (decreasing for O

2

) gas read-

ing at or above the alarm 1 setpoint

•

Alarm 1 LED is on

•

Gas reading alternates with
ALARM-1 message

•

If installed and set to
activate for alarm 1, strobe
flashes

•

Pulsing tone

Alarm 2

1

Increasing gas reading at or above the
alarm 2 setpoint

•

Alarm 2 LED is on

•

Gas reading alternates with
ALARM-2 message

•

If installed and set to
activate for alarm 2, strobe
flashes

•

Pulsing tone

Fail

•

Disconnected or misconnected
detector head wiring

•

Display reading at -10% of full scale
or lower

•

Defective components

•

Fail LED is on

•

FAIL message replaces
gas reading

•

If installed, strobe flashes

•

Steady tone

Low Power

DC power source less than 18.5 volts.

•

Fail LED is on

•

LowPower message and
actual voltage of incoming
DC power

•

None

*

1

If the Beacon 110 is in both an alarm 1 and an alarm 2 condition, both alarm LEDs

are on and the display alternates between the gas reading and the ALMS 1&2 message.