Alarm indications – RKI Instruments Beacon 110 User Manual

Page 26

Advertising
background image

22

Beacon 110 Operator’s Manual

Alarm Indications

NOTE:

The Beacon 110 includes alarm on and alarm off delay settings for alarm 1 and
alarm 2. The alarm indications described in this section operate according to
the factory set alarm settings. See Table 7 on page 27 for all the factory
settings.

NOTE:

You can select normally energized (N. EN) or normally de-energized (N. DE-
EN) alarm 1 and alarm 2 relay settings in Configuration Mode. The following
sections describe the standard factory setting for these relays which is
N. DE-EN.

The fail relay is set as normally energized in the firmware and is not user-
adjustable.

Table 6: Visual and Audible Alarm Indications

Condition

Cause

Visual Indication(s)

Audible

Indication

Alarm 1

1

Increasing (decreasing for O

2

) gas read-

ing at or above the alarm 1 setpoint

Alarm 1 LED is on

Gas reading alternates with
ALARM-1 message

If installed and set to
activate for alarm 1, strobe
flashes

Pulsing tone

Alarm 2

1

Increasing gas reading at or above the
alarm 2 setpoint

Alarm 2 LED is on

Gas reading alternates with
ALARM-2 message

If installed and set to
activate for alarm 2, strobe
flashes

Pulsing tone

Fail

Disconnected or misconnected
detector head wiring

Display reading at -10% of full scale
or lower

Defective components

Fail LED is on

FAIL message replaces
gas reading

If installed, strobe flashes

Steady tone

Low Power

DC power source less than 18.5 volts.

Fail LED is on

LowPower message and
actual voltage of incoming
DC power

None

*

1

If the Beacon 110 is in both an alarm 1 and an alarm 2 condition, both alarm LEDs

are on and the display alternates between the gas reading and the ALMS 1&2 message.