RKI Instruments Beacon 110 User Manual

Page 44

Advertising
background image

40

Beacon 110 Operator’s Manual

Reset Switch
Not Working

The buzzer does not
silence when you
press the reset
switch.

The alarm 1 or
alarm 2 circuit does
not reset when you
press the reset
switch after the
alarm condition
passes.

The reset switch is
disconnected or
misconnected.

The reset switch is
malfunctioning.

1.

Verify that the wiring to the ALARM
RESET
(2) terminals of the Alarm/
Controller Terminal Strip is correct and
secure.

2.

If the reset switch difficulties continue,
contact RKI for further instruction.

If Installed,
Option Strobe
Not Working

The strobe does not
flash when an alarm
1 or alarm 2
condition occurs.

The strobe does not
flash when a fail
condition occurs.

The strobe is not
setup to activate in an
alarm 1 or alarm 2
condition.

The strobe is not
connected to the
strobe terminal strip
properly.

The strobe is
malfunctioning.

1.

Verify that the strobe is setup properly for
the desired alarm operation in
Configuration Mode. See “Chapter 5:
Configuration Mode” on page 26.

2.

Verify that the strobe is wired properly to
the strobe terminal strip. The red wire goes
to the + terminal and the black wire goes
to the - terminal.

Table 9: Troubleshooting the Beacon 110 (Continued)

Condition

Symptom(s)

Probable Causes

Recommended Action