Chapter 5: configuration mode, Overview, Viewing & changing beacon 110 parameters – RKI Instruments Beacon 110 User Manual

Page 30

Advertising
background image

26

Beacon 110 Operator’s Manual

Chapter 5: Configuration Mode

Overview

This chapter describes how to view and change Beacon 110 parameters using
Configuration Mode. It is accessed using the program buttons.

Configuration Mode includes a 5-minute time-out feature. If you do not press a control
button for 5 minutes, the Beacon 110 automatically returns to normal operation.

NOTE:

If the Beacon 110 returns to normal operation because of a time-out, it enters a
warm-up period just as it does when it is first turned on.

If you are installing a new Beacon 110, it has been set up at the factory. Use
Configuration Mode only if you want to change the Beacon 110’s setup. If you
want to change the detector type see “Chapter 6: Input Mode” on page 29.

Viewing & Changing Beacon 110
Parameters

1.

While in normal operation, simultaneously press and hold the UP/YES and ENTER
buttons for 5 seconds to enter Configuration Mode. Release the buttons when the
following screen appears.

2.

If you want to exit Configuration Mode, press and release the DOWN/NO button and
the Beacon 110 will return to normal operation.

If you want to continue in Configuration Mode, press and release the UP/YES button.
The target gas and the full scale will be displayed for a few seconds before the first
adjustable parameter, the alarm 1 setpoint, is displayed.

3.

If you want to change the currently displayed parameter, use the UP/YES and
DOWN/NO buttons to adjust it to the desired setting, then press ENTER to continue to
the next parameter.

If the currently displayed parameter is OK, press the ENTER button to proceed to the
next parameter.

Table 7 lists the Beacon 110 parameters you can set. Table 7 also lists the factory set
value for each parameter.

Enter

Config?