Beacon 110 Rig Monitor Operator’s Manual

Connecting Recorders

Perform the following procedure to connect an analog signal recording device to the Rig Monitor.
The output at the recorder output terminals is a 4 - 20 mA signal that is proportional to the detection
range of the H

2

S detector head connected to the Rig Monitor’s Fail or Alarm 2 terminals. The

Alarm 1 terminals are factory wired and not available for field use.

1.

Disconnect the battery clamps from the + and - terminals of the 12 VDC battery.

2.

Open the housing door, and locate the recorder output terminals on the controller terminal
strip. See Figure 1 to assist you in locating the recorder output terminals. They are labelled 4 -
20 mA OUTPUT +
and 4 - 20 mA OUTPUT -.

3.

Place the power switch in the off position.

4.

Install an appropriately rated cable bushing in the Rig Monitor housing. Both factory supplied
conduit hubs are used in the Rig Monitor, so you will need to drill a hole in the housing for a
conduit hub and cable bushing.

5.

Guide the wiring from the recording device through the new cable bushing.

6.

Connect the leads from the recording device to the analog output terminal strip as shown in
Figure 9 below.

Figure 9: Recorder Output Wiring

4-20 mA

OUTPUT

Recording Device,
500 Ohms Max
Impedance