Digester Gas Monitor Operator’s Manual

Alarm Indications • 41

NOTE: You can set the channel alarm relays to be either all normally energized or all

normally de-energized in the Global Menu. The following sections describe the
factory settings of normally de-energized for the channel relays. The fail relay is
factory-set as normally energized and is not user adjustable. See “Viewing and
Changing Global Parameters” on page 47 for instructions to change the channel
alarm relays.

Alarm 1 Condition

This section describes the indications for an alarm 1 condition and suggests responses to
an alarm 1 condition.

Alarm 1 Condition Indications

When the gas reading of an active channel reaches the alarm 1 setpoint, the Digester Gas
Monitor senses an alarm 1 condition. The Digester Gas Monitor alerts you to an alarm 1
condition as follows:

the alarm 1 LED turns on

the gas reading in alarm 1 condition alternates with the ALARM-1 message

the buzzer sounds a pulsing tone

the applicable alarm 1 channel relay energizes

if installed and set to activate in an alarm 1 condition, the horn/strobe flashes and
sounds a pulsing tone

NOTE: The oxygen alarm 1 condition has a 30 second factory set delay. The delay may

be changed in the Configuration Menu.

Fail

Disconnected or
misconnected
detector wiring

Display reading below
-10% of full scale or
lower

Malfunctioning
components

Fail LED is on

FAIL message replaces the
gas reading

If installed and set to activate
for fail, horn/strobe flashes

NOTE: There is a 30 second delay
on the fail indications.

Buzzer sounds a
steady tone

If installed and set to
activate for a fail
condition, the horn/
strobe sounds a
pulsing tone

Flow Fail

Flow to system falls
below 1.6 SCFH

Display alternates between
FLOW FAIL and normal
screen

If installed, the horn/strobe
activates

A 60 second fresh air purge is
initialized

Flow through system will be
stopped

Buzzer sounds a
steady tone

If installed, the horn/
strobe sounds a
pulsing tone

Low
Battery

No AC power and DC
power source (primary or
backup) less than 18.5
volts.

FAIL LED is on

Display shows LOW POWER
STANDBY
message and the
input DC voltage

None

Table 6: Visual and Audible Alarm Indications

Condition

Cause

Visual Indication(s)

Audible Indication