Digester Gas Monitor Operator’s Manual

Specifications • 3

Specifications

Table 1 lists specifications for the Digester Gas Monitor.

Table 1: Digester Gas Monitor Specifications

Description

Specification

Detection
Range

Methane

(CH

4

)

Oxygen (O

2

)

Carbon

Dioxide (CO

2

)

Hydrogen Sulfide (H

2

S)

0 - 100%
volume

0 - 25%
volume

0 - 50%
volume

0 - 1000
ppm

0 - 3000
ppm

0 - 5000
ppm

Alarm Points

Alarm 1:
100% volume
Alarm 2:
100% volume
Alarm 3:
100% volume

Alarm 1:
4% volume
(increasing)
Alarm 2:
25% volume
(increasing)
Alarm 3:
25% volume
(increasing)

Alarm 1:
50% volume
Alarm 2:
50% volume
Alarm 3:
50% volume

Alarm 1:
1000 ppm
Alarm 2:
1000 ppm
Alarm 3:
1000 ppm

Alarm 1:
3000 ppm
Alarm 2:
3000 ppm
Alarm 3:
3000 ppm

Alarm 1:
5000 ppm
Alarm 2:
5000 ppm
Alarm 3:
5000 ppm

NOTE: There are different versions of the Digester Gas Monitor. Some versions may
not have all four gas sensors installed.

Input Power

100/115/220V ~ ±10%, 50/60Hz, 1.0/1.0/0.5A
or
24 V

± 10%, 2.5A VDC

Maximum
Compressed
Air Sample
Pressure

140 PSI

Minimum
Regulator
Output PSI
Required

No Sample Lines Connected: Regulator output set to 25 PSI
Maximum Recommended Sample Lines Connected: Regulator output set to
45 PSI

Recommended
Sample Flow
Rate

3.0 SCFH

Compressed
Air Usage

63 liters maximum per detection cycle

Construction
(housing)

Fiberglass/polyester with lexan window (NEMA 4X)

Dimensions

24.0 in. H x 24.0 in. W x 10.0 in. D
(61.0 cm H x 61.0 cm W x 25.4 cm D)

Weight

45 lbs. (including horn/strobe)