Digester Gas Monitor Operator’s Manual

Supported Modbus Functions • 75

Registers 40025 - 40027

The 6 bytes (characters) in these registers contain the channel gas reading in ASCII
characters.

Registers 40028 - 40029

The 4 bytes (characters) in registers 40028 and 40029 represent the channel gas units in
ASCII characters.

Registers 40030 - 40043, Channel 3 Information

Register 40030

Table 18 below shows the information in register 40030.

Registers 40031 & 40032

The 32 bits in registers 40031 and 40032 contain the channel 2 numerical reading in
single precision floating point IEEE format.

Register 40033

The 16 bits in register 40033 contain the channel 2 numerical reading in integer form
omitting the sign (+ or -) and the decimal point.

Register 40034

Table 19 below shows the information in register 40034.

Table 18: Register 40030

Channel Operational State

(MS-Byte)

Channel Status Bits

(LS-Byte)

0 = (this code is not used)

1 = Standby

2 = Normal Operation

3 = Warm Up

4 = Fail

5 = Post-Calibration

6 = Low Power

Bit-7 (msb) = Relay-1 (1 = energized)

Bit-6 = Relay-2 (1 = energized)

Bit-5 = (this bit is not used)

Bit-4 = Alarm-1 (1 = asserted)

Bit-3 = Alarm-2 (1 = asserted)

Bit-2 = Alarm-3 (1 = asserted)

Bits[1:0] = Channel Usage Code
[00] = Not Used

[01] = Standby

[10] = Active

[11] = unused code

Table 19: Register 40034

Channel Reading Sign (+/-)

(MS-Byte)

Channel Decimal Point Position

(LS-Byte)

0 = Positive (+)

1 = Negative (-)

0 = No Decimal Point

1 = .x

2 = .xx

3 = .xxx