70 • Using the Digester Gas Monitor in a 4-wire Modbus System

Digester Gas Monitor Operator’s Manual

Figure 22: Multiple Digester Gas Monitors in a Two Branch Configuration

Using the Digester Gas Monitor in a
4-wire Modbus System

Although the Digester Gas Monitor is a 2-wire Modbus RTU device, it can be used with a
4-wire Modbus controller if the system wiring is modified as follows:

Connect the controller’s TxD0 and RxD0 wires together and use this connection as
the 2-wire Modbus D0 signal.

Connect the controller’s TxD1 and RxD1 wires together and use this connection as
the 2-wire Modbus D1 signal.

Connect these D0 and D1 signals and the common wire from the controller to the 2-
wire Modbus Network of Digester Gas Monitors.

Modbus Menu

The Modbus Menu allows you to configure various parameters relating to the Modbus
setup of the Digester Gas Monitor. The Modbus Menu includes a 5-minute timeout feature.
If you do not press a control switch for 5 minutes, the Digester Gas Monitor automatically
returns to Standby Mode.

NOTE: If the Digester Gas Monitor returns to Standby Mode because of a timeout, it

enters a warm-up period just as it does when it is first turned on.

1.

While in Standby Mode, simultaneously press and hold the ENTER and DOWN/NO
buttons for approximately 5 seconds to enter the Modbus Menu. Release the buttons
when the

You Have Entered the MODBUS Menu

message appears on the display.

Digester Gas Analyzer

Termination Jumper

Installed

ID=4

ID=31

ID=32

Digester Gas A nalyzer

Termination Jumper

Installed

RS-485

Modbus Master

Up to 32 Digester Gas A nalyzers can be connected without a repeater

ID=3

Digester Gas Analyzer

Termination Jumper

Not Installed

Digester Gas Analyzer

Termination Jumper

Not Installed

Digester Gas A nalyzer

Termination Jumper

Not Installed

Digester Gas A nalyzer

Termination Jumper

Not Installed

ID=2

ID=1

RS-485