Installation and Wiring Chapter 2

Wiring

Important points to remember about wiring:

Always use tinned copper wire.

Wire with an insulation rating of 600V or greater is recommended.

Control wires should be separated from power wires by at least 0.3 meters
(1 foot).

All control wires should be shielded cable with the shield earthed on one
end of the cable.

Table 1 - DriveGuard Safe Torque Off Option Terminal Block Specifications

Table 2 - Wire Types

Table 3 - DriveGuard Safe Torque Off Option Terminals Description

Wire Size Range

(1)

(1) Maximum / minimum that the terminal block will accept - these are not

recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

1.5 mm

2

(16 AWG)

0.14 mm

2

(26 AWG)

0.25 N•m
(2.2 lb•in)

0.22 N•m
(1.9 lb•in)

Wire Type(s)

Description

Minimum
Insulation Rating

Unshielded Per US NEC or applicable

national or local code

NOT RECOMMENDED 300V,

60 degrees C
(140 degrees F)

Shielded

Multi-conductor shielded cable
such as Belden 8770(or equiv.)

0.750 mm

2

(18AWG),

3 conductor, shielded.

No. Signal

Description

1

+24V DC

Connections for user-supplied power
to energize coil.
33.3 mA typical, 55 mA maximum.

2

24V Common

3

Monitor - N.C.

Normally closed contacts for
monitoring relay status.
Maximum Resistive Load:
250V AC / 30V DC / 50 VA / 60 Watts
Maximum Inductive Load:
250V AC / 30V DC / 25 VA / 30 Watts

4

Common - N.C.