Rockwell Automation Publication 20D-UM007G-EN-P - March 2012

27

Installation and Wiring Chapter 2

Configure Digital Outputs

Digital Output 1 and 2 (TB2 Terminals 3, 4, and 5) and Relay Output 3
(TB2 Terminals 6, 7, and 8) can be configured to activate external logic in the
event the safety enable diagnostic routine results in an F45 “Enable Health”
fault.

1. Set Par 147 [FW Functions En], Bit 14 “Digital Outs” to 1 (True).

2. Set Par 845 [Dig Out1 Sel], Par 850 [Dig Out2 Sel] or Par 855 [Rly Out3

Sel] to option 0 “User Select”.

3. Link Par 846 [Dig Out1 Data], Par 851 [Dig Out2 Data] or Par 856 [Rly

Out3 Data] to Par 324 [Fault Status 2]. See “Linking Parameters” below.

4. Set Par 847 [Dig Out1 Bit], Par 852 [Dig Out2 Bit] or Par 857 [Rly Out3

Bit] to 12. Par 324 Bit 12 = EnableHealth status.

Linking Parameters

Use the following procedure to establish a link between Par 846 [Dig Out1
Data], Par 851 [Dig Out2 Data] or Par 856 [Rly Out3 Data] and Par 324
[Fault Status 2].

1. Using the drive’s Human Interface Module (HIM), select Parameter from

the Main Menu and press the Enter key.

2. Using the HIM keypad, enter 846, 850, or 856 and press the Enter key.

The parameter value screen will appear.

3. Press ALT and then View (Sel). Next, press the Up or Down Arrow to

change “Present Value” to “Defined Link.” Press the Enter key.

4. Press the Enter key to select the “Link” field. Using the HIM keypad,

enter 324 as the Source Parameter Number and press the Enter key.

The linked parameter can now be viewed two different ways by
repeating the steps above and selecting “Preset Value” or “Define
Link.” If an attempt is made to edit the value of a linked parameter,
“Parameter is Linked!” will be displayed, indicating that the value is
coming from a source parameter and cannot be edited.

5. To remove a link, repeat the steps above and change the source parameter

to zero (0).