Rockwell Automation Publication 20D-UM007G-EN-P - March 2012

33

Description of Operation Chapter 3

Application Considerations

When the hazard analysis for the overall machine determines the need for
external mechanical brakes or other stopping means, the external means shall
be activated after the removal of power for Stop Category 0.

If the Safe Torque Off option sticks ON, the motor will stop on command
due to the enable input. The system cannot be reset when this fault condition
exists.

Example 3 - All Drives
Safe Torque Off Connection with Controlled Stop Action, Dual
Channel

Figure 4 - Stop Category 1 – Controlled

Circuit Status

Circuit shown with guard door closed and system ready for normal operation.

+24V DC
Common

+24V DC

GuardMaster

Trojan

Stop

Start

A1

S21 S11 S52 S12

A2 X1 X2

13 23

14 24

S33

Y2

S34

Y1

X3

37 47 57

38 48 58

X4

S22

Y39 Y40

Minotaur

MSR138DP

Gate

+24V DC

PowerFlex
700S/700L

Stop

Start

Start/Stop Common

24V DC Common

3

4

1

2

Safe Off Option

AC Line

Input Power

Common

Enable

M

Gate Control

Power Supply

Gate Control

Circuit