Rockwell Automation 20D-P2-DG03 DriveGuard Safe Torque Off Option for PowerFlex 700S Phase II and 700L Drives User Manual

Page 32

Advertising
background image

32

Rockwell Automation Publication 20D-UM007G-EN-P - March 2012

Chapter 3 Description of Operation

Example 2 - PowerFlex 700S Drives, Frames 9…14 and
PowerFlex 700L Drives, Frames 3A and 3B
Safe Torque Off Connection with Coast-to-Stop Action, Dual
Channel

Figure 3 - Stop Category 0 – Coast

Circuit Status

Circuit shown with guard door closed and system ready for normal drive
operation.

Operating Principle

This is a dual channel system with monitoring of the Safe Torque Off circuit
and drive. Opening the guard door will switch the input circuits (S11-S12 &
S21-S22) to the Minotaur monitoring safety relay unit. The output circuits
(13-14 & 23-24) cause the drive Enable circuit to trip and the motor will
coast to stop. After the programmed delay, the timed output circuits (57-58)
will cause the Safe Torque Off option circuit to trip. To restart the drive, the
Minotaur safety relay must first be reset followed by a valid start command to
the drive.

+24V DC
Common

+24V DC

GuardMaster

Trojan

Stop

Start

A1

S21 S11 S52 S12

A2 X1 X2

13 23

14 24

S33

Y2

S34

Y1

X3

37 47 57

38 48 58

X4

S22

Y39 Y40

Minotaur

MSR138DP

Gate

+24V DC

PowerFlex
700S/700L

Stop

Start

Start/Stop Common

24V DC Common

3

4

1

2

Safe Off Option

AC Line

Input Power

Common

Enable

M

Gate Control

Power Supply

Gate Control

Circuit