Rockwell Automation 20P, 23P PowerFlex DC Drive and SAR Control Circuit Board Installation Instructions User Manual

Page 12

Advertising
background image

Publication 20P-IN004B-EN-P

12

Step 5C: Remove the 115V AC to 24V DC Converter Board

If the optional 115V AC to 24V DC converter board is not installed, continue
with Step 6:

Remove the Existing Control Board on page 13

.

1. Remove the plug-in I/O terminal blocks.

2. Remove the two screws that secure the I/O converter board to the stand-offs

on the control board and remove the converter board.

3. Remove the two stand-offs and washers that support the converter board on

the control board.

Remove two screws
Tightening torque:
1.0 N•m (8.9 lb•in)

Remove two stand-offs
Tightening torque:
1.0 N•m (8.9 lb•in)