What you need to do, Step 1: save the parameter configuration, Step 2: remove power from the drive – Rockwell Automation 20P, 23P PowerFlex DC Drive and SAR Control Circuit Board Installation Instructions User Manual

Page 2

Advertising
background image

Publication 20P-IN004B-EN-P

2

What You Need to Do

To install the Control board:

❐ Step 1:

Save the Parameter Configuration

❐ Step 2:

Remove Power from the Drive

❐ Step 3:

Remove the Drive Covers

❐ Step 4:

Remove the Communication Adapter and EMI Shield

❐ Step 5:

Remove the Existing Connections and Option Board(s)

❐ Step 6:

Remove the Existing Control Board

❐ Step 7:

Install the New Control Board

❐ Step 8:

Wire the Control Board

❐ Step 9:

Document the Change

Step 1: Save the
Parameter Configuration

If possible, save the drive and adapter parameter configuration to a Human
Interface Module (HIM) Set or by up loading the drive and adapter parameters
to an offline database file using DriveExecutive™. Refer to the PowerFlex DC
Digital Drive User Manual
, publication

20P-UM001

, for information on using

the HIM or the on-line Help provided with DriveExecutive.

Step 2: Remove Power
from the Drive

Remove and lock-out all incoming power to the drive.

ATTENTION: Remove power before making or breaking cable
connections. When you remove or insert a cable connector with
power applied, an electrical arc may occur. An electrical arc can
cause personal injury or property damage by:

• sending an erroneous signal to your system’s field devices,

causing unintended machine motion

• causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.

L1

L2

L3

O

I