Mod status indicator, Mod status indicator -3 – Rockwell Automation 22-COMM-C ControlNet Adapter User Manual
Page 107

Troubleshooting
8-3
MOD Status Indicator
Status
Cause
Corrective Action
Off
The adapter is not powered or
not properly connected to the
drive.
• Securely connect the adapter to the drive
using the Internal Interface (ribbon) cable.
• Apply power to the drive (or adapter if
mounted in a DSI External Comms Kit).
Flashing
Red
The adapter has failed the
firmware test.
• Cycle power to the drive (or adapter if
mounted in a DSI External Comms Kit).
• If cycling power does not correct the
problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.
• If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
Solid
Red
The adapter has failed the
hardware test.
• Cycle power to the drive (or adapter if
mounted in a DSI External Comms Kit).
• Replace the adapter.
Flashing
Green
The adapter is operational, but
is not transferring I/O data.
• Place the scanner in RUN mode.
• Program the controller to recognize and
transmit I/O to the adapter.
• Configure the adapter for the program in
the controller.
Solid
Green
The adapter is operational and
transferring I/O data.
No action required.