Advanced Group Parameters

No.

Parameter

Min/Max

Display/Options

Default

A051

A052

A053

A054

[Digital In1 Sel]
I/O Terminal 05
[Digital In2 Sel]
I/O Terminal 06
[Digital In3 Sel]
I/O Terminal 07
[Digital In4 Sel]
I/O Terminal 08

0/27

0 = “Not Used”
1 = “Acc & Dec 2”
2 = “Jog”
3 = “Aux Fault”
4 = “Preset Freq”
5 = “Local”

(1)

6 = “Comm Port”
7 = “Clear Fault”
8 = “RampStop,CF”
9 = “CoastStop,CF”
10 = “DCInjStop,CF”
11 = “Jog Forward”
12 = “Jog Reverse”
13 = “10V In Ctrl”

14 = “20mA In Ctrl”
15 = “PID Disable”
16 = “MOP Up”
17 = “MOP Down”
18 = “Timer Start”
19 = “Counter In”
20 = “Reset Timer”
21 = “Reset Countr”
22 = “Rset Tim&Cnt”
23 = “Logic In1”
24 = “Logic In2”
25 = “Current Lmt2”
26 = “Anlg Invert”
27 = “EM Brk Rlse”

4

4

5

11

(1)

Important: Speed source for IP66, NEMA/
UL Type 4X rated drives comes from A069
[Internal Freq].

A055 [Relay Out Sel]

0/24

0 = “Ready/Fault”
1 = “At Frequency”
2 = “MotorRunning”
3 = “Reverse”
4 = “Motor Overld”
5 = “Ramp Reg”
6 = “Above Freq”
7 = “Above Cur”
8 = “Above DCVolt”
9 = “Retries Exst”
10 = “Above Anlg V”
11 = “Logic In 1”
12 = “Logic In 2”

13 = “Logic 1 & 2”
14 = “Logic 1 or 2”
15 = “StpLogic Out”
16 = “Timer Out”
17 = “Counter Out”
18 = “Above PF Ang”
19 = “Anlg In Loss”
20 = “ParamControl”
21 = “NonRec Fault”
22 = “EM Brk Cntrl”
23 = “Above Fcmd”
24 = “MsgControl” (for
FRN 6.01 and later)

0

A056 [Relay Out Level]

0.0/9999

0.1

0.0

A058
A061

[Opto Out1 Sel]
[Opto Out2 Sel]

0/24

See A055 for Options.

2
1

A059
A062

[Opto Out1 Level]
[Opto Out2 Level]

0.0/9999

0.1

0.0

A064 [Opto Out Logic]

0/3

1

0

A055, A058 & A061 Setting

A056, A059 & A062 Min/Max

6

0/400 Hz

7

0/180%

8

0/815 Volts

10

0/100%

16

0.1/9999 Secs

17

1/9999 Counts

18

1/180 degs

20

0/1

23

0/400 Hz

A064 Option

Opto Out1 Logic

Opto Out2 Logic

0

NO (Normally Open)

NO (Normally Open)

1

NC (Normally Closed)

NO (Normally Open)

2

NO (Normally Open)

NC (Normally Closed)

3

NC (Normally Closed)

NC (Normally Closed)

See the PowerFlex 40 User Manual for more information on parameters.