I/o wiring recommendations (3), I/o wiring recommendations, I/o terminal block specifications – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 7: English-7

Advertising
background image

English-7

Input Power Conditions

I/O Terminal Block Specifications

Refer to the PowerFlex 40 User Manual for recommendations on
maximum power and control cable length.

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line reactance)

Install Line Reactor

(2)

or Isolation Transformer

or Bus Inductor – 5.5-11 kW
(7.5-15 HP) drives only

(2)

Refer to Appendix B of the PowerFlex 40 User Manual for accessory ordering
information.

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Install Line Reactor

or Isolation Transformer

Line has frequent power interruptions

Line has intermittent noise spikes in excess of
6000V (lightning)

Phase to ground voltage exceeds 125% of normal
line to line voltage

Remove MOV jumper to ground.

or Install Isolation Transformer
with grounded secondary if
necessary.

Ungrounded distribution system

240V open delta configuration (stinger leg)

(1)

(1)

For drives applied on an open delta with a middle phase grounded neutral system, the
phase opposite the phase that is tapped in the middle to the neutral or earth is
referred to as the “stinger leg,” “high leg,” “red leg,” etc. This leg should be identified
throughout the system with red or orange tape on the wire at each connection point.
The stinger leg should be connected to the center Phase B on the reactor. Refer to the
PowerFlex 40 User Manual for specific line reactor part numbers.

Install Line Reactor

I/O Wiring Recommendations

(3)

Wire Type(s)

(4)

Description

Minimum Insulation
Rating

Belden 8760/9460
(or equiv.)

0.8 mm

2

(18AWG), twisted pair, 100% shield

with drain.

300V
60 degrees C
(140 degrees F)

Belden 8770
(or equiv.)

0.8 mm

2

(18AWG), 3 conductor, shielded for

remote pot only.

(3)

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

(4)

Stranded or solid wire.

Frame

Maximum Wire Size

(5)

Minimum Wire Size

(5)

Torque

B & C

1.3 mm

2

(16 AWG)

0.2 mm

2

(24 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)

(5)

Maximum / minimum that the terminal block will accept - these are not
recommendations.

Advertising