Power Terminal Block

Power Terminal Block Specifications

Power Wiring

Power Wire Rating

Recommended Copper
Wire

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/
RHW-2

Anixter OLF-7xxxxx,
Belden 29501-29507 or
equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F)
RHH/RHW-2

Anixter 7V-7xxxx-3G
Shawflex 2ACD/3ACD or
equivalent

Terminal

(1)

Description

R/L1, S/L2

1-Phase Input

R/L1, S/L2, T/L3 3-Phase Input

U/T1

To Motor U/T1

=

Switch any two motor
leads to change
forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

P2, P1

DC Bus Inductor Connection (C Frame drives only.)

The C Frame drive is shipped with a jumper between
Terminals P2 and P1. Remove this jumper only when a DC
Bus Inductor will be connected. Drive will not power up
without a jumper or inductor connected.

DC+, DC-

DC Bus Connection

BR+, BR-

Dynamic Brake Resistor Connection

Safety Ground - PE

(1)

Important: Terminal screws may become loose during shipment. Ensure that all
terminal screws are tightened to the recommended torque before applying power to
the drive.

Frame

Maximum Wire Size

(2)

Minimum Wire Size

(2)

Torque

B

5.3 mm

2

(10 AWG)

1.3 mm

2

(16 AWG)

1.7-2.2 N-m (16-19 lb.-in.)

C

8.4 mm

2

(8 AWG)

1.3 mm

2

(16 AWG)

2.9-3.7 N-m (26-33 lb.-in.)

(2)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

P2

P1

BR+

BR-

DC- DC+

B Frame

C Frame