English-5, Input/output ratings approvals, Control output – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 5: Fuses and circuit breakers, Protective features, Dynamic braking

Advertising
background image

English-5

(3)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M

Motor Protection Circuit Breakers Application Ratings

.

(4)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.

(5)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.

Input/Output Ratings

Approvals

Output Frequency: 0-400 Hz (Programmable)

Efficiency: 97.5% (Typical)

Digital Control Inputs (Input Current = 6mA)

Analog Control Inputs

SRC (Source) Mode:

18-24V = ON
0-6V = OFF

SNK (Sink) Mode:

0-6V = ON
18-24V = OFF

4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum

Control Output

Programmable Output (form C relay)
Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC

Opto Outputs
30V DC, 50mA
Non-inductive

Analog Outputs (10 bit)
0-10V, 1k ohm Min.
4-20mA, 525 ohm Max.

Fuses and Circuit Breakers

Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Recommended Circuit Breakers: HMCP circuit breakers or equivalent.

Protective Features

Motor Protection: I

2

t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)

Overcurrent: 200% hardware limit, 300% instantaneous fault

Over Voltage:

100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
460-600V AC Input – Trip occurs at 1005V DC bus voltage (equivalent to 711V AC incoming line)

Under Voltage: 100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)

200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
460-600V AC Input – If P042 = 3 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);

If P042 = 2 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)

Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs

Faultless Power Ride Through: 100 milliseconds

Dynamic Braking

Internal brake IGBT included with all ratings except No Brake versions. Refer to Appendix B of the PowerFlex 40 User Manual
for DB resistor ordering information.

UL

®

LIS

TED 966X

IND

CO N T E

Q

UL508C

UL

®

LIS

TED 966X

IND

CO N T E

Q

C

CSA 22.2

EMC Directive 89/336

LV:

EN 50178, EN 60204

EMC: EN 61800-3, EN 50081-1, EN 50082-2