English-18 – Rockwell Automation 22B PowerFlex 40 Quick Start FRN 5.xx - 6.xx User Manual

Page 18

Advertising
background image

English-18

A084 [Boost Select]

0/14

Settings in % of base voltage.

8
7 4-11 kW

(5-15 HP)

Only active when A125 [Torque Perf Mode] is
set to 0 “V/Hz”.

0 = “Custom V/Hz”
Variable Torque

Constant Torque

1 = “30.0, VT”

5 = “0.0, no IR”

10 = “10.0, CT”

2 = “35.0, VT”

6 = “0.0”

11 = “12.5, CT”

3 = “40.0, VT”

7 = “2.5, CT”

12 = “15.0, CT”

4 = “45.0, VT”

8 = “5.0, CT”

13 = “17.5, CT”

9 = “7.5, CT”

14 = “20.0, CT”

A085 [Start Boost]

0.0/25.0%

0.1%

2.5%

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.

A086 [Break Voltage]

0.0/100.0%

0.1%

25.0%

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.

A087 [Break Frequency]

0.0/400.0 Hz

0.1 Hz

15.0 Hz

Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.

A088 [Maximum Voltage]

20/Rated Volts

1 VAC

Rated Volts

A089 [Current Limit 1]

0.1/(Drive Amps

×

1.8) 0.1 Amps

Amps

×

1.5

A090 [Motor OL Select]

0/2

0 = “No Derate”

1 = “Min Derate”
2 = “Max Derate”

0

A091 [PWM Frequency]

2.0/16.0 kHz

0.1 kHz

4.0 kHz

A092 [Auto Rstrt Tries]

0/9

1

0

A093 [Auto Rstrt Delay]

0.0/300.0 Secs

0.1 Secs

1.0 Secs

A094 [Start At PowerUp]

0/1

0 = “Disabled”

1 = “Enabled”

0

A095 [Reverse Disable]

0/1

0 = “Rev Enabled”

1 = “Rev Disabled”

0

A096 [Flying Start En]

0/1

0 = “Disabled”

1 = “Enabled”

0

A097 [Compensation]

0/3

0 = “Disabled”
1 = “Electrical”

2 = “Mechanical”
3 = “Both”

1

A098 [SW Current Trip]

0.0/(Drive Amps

×

2)

0.1 Amps

0.0 (Disabled)

A099 [Process Factor]

0.1/999.9

0.1

30.0

A100 [Fault Clear]

0/2

0 = “Ready/Idle”

1 = “Reset Fault”
2 = “Clear Buffer”

0

A101 [Program Lock]

0/9999

0 = “Unlocked”

1 = “Locked”

0

A102 [Testpoint Sel]

400/FFFF

1 Hex

400

A103 [Comm Data Rate]

0/5

0 = “1200”
1 = “2400”
2 = “4800”

3 = “9600”
4 = “19.2K”
5 = “38.4K”

3

Power to drive must be cycled before any
changes will affect drive operation.

A104 [Comm Node Addr]

1/247

1

100

Power to drive must be cycled before any
changes will affect drive operation.

A105 [Comm Loss Action]

0/3

0 = “Fault”
1 = “Coast Stop”

2 = “Stop”
3 = “Continu Last”

0

A106 [Comm Loss Time]

0.1/60.0 Secs

0.1 Secs

5.0 Secs

A107 [Comm Format]

0/5

0 = “RTU 8-N-1”
1 = “RTU 8-E-1”
2 = “RTU 8-O-1”

3 = “RTU 8-N-2”
4 = “RTU 8-E-2”
5 = “RTU 8-O-2”

0

Power to drive must be cycled before any
changes will affect drive operation.

A108 [Language]

1/10

1 = “English”
2 = “Français”
3 = “Español”
4 = “Italiano”
5 = “Deutsch”

6 = “Reserved”
7 = “Português”
8 = “Reserved”
9 = “Reserved”
10 = “Nederlands”

1

A109 [Anlg Out Setpt]

0.0/100.0%

0.1%

0.0%

A110 [Anlg In 0-10V Lo]

0.0/100.0%

0.1%

0.0%

A111 [Anlg In 0-10V Hi]

0.0/100.0%

0.1%

100.0%

A112 [Anlg In4-20mA Lo]

0.0/100.0%

0.1%

0.0%

A113 [Anlg In4-20mA Hi]

0.0/100.0%

0.1%

100.0%

A114 [Slip Hertz @ FLA]

0.0/10.0 Hz

0.1 Hz

2.0 Hz

A115 [Process Time Lo]

0.00/99.99

0.01

0.00

No.

Parameter

Min/Max

Display/Options

Default

See the PowerFlex 40 User Manual for more information on parameters.