Control I/O Terminal Designations

No. Signal

Default

Description

Param.

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Analog Output Select
DIP Switch

0-10V

Sets analog output to either voltage or current. Setting must match
A065 [Analog Out Sel].

Sink/Source
DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch
setting.

01

Stop

(1)

Coast

The factory installed jumper or a normally closed
input must be present for the drive to start.

P036

(1)

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default.
To disable reverse operation, see A095 [Reverse
Disable].

P036, P037

03

Direction/Run REV Not Active

P036, P037,
A095

04

Digital Common

For digital inputs. Electronically isolated with digital
inputs from analog I/O and opto outputs.

05

Digital Input 1

Preset Freq

Program with A051 [Digital In1 Sel].

A051

06

Digital Input 2

Preset Freq

Program with A052 [Digital In2 Sel].

A052

07

Digital Input 3

Local

Program with A053 [Digital In3 Sel].

A053

08

Digital Input 4

Jog Forward

Program with A054 [Digital In4 Sel].

A054

09

Opto Common

For opto-coupled outputs. Electronically isolated with
opto outputs from analog I/O and digital inputs.

11

+24V DC

Referenced to Digital Common.
Drive supplied power for digital inputs.
Maximum output current is 100mA.

12

+10V DC

Referenced to Analog Common.
Drive supplied power for 0-10V external
potentiometer.
Maximum output current is 15mA.

P038

13

±10V In

(2)

Not Active

For external 0-10V (unipolar) or ±10V (bipolar) input
supply (input impedance = 100k ohm) or
potentiometer wiper.

P038,
A051-A054,
A123, A132

14

Analog Common

For 0-10V In or 4-20mA In. Electronically isolated
with analog inputs and outputs from digital I/O and
opto outputs.

15

4-20mA In

(2)

Not Active

For external 4-20mA input supply
(input impedance = 250 ohm).

P038,
A051-A054,
A132

16

Analog Output

OutFreq 0-10

The default analog output is 0-10V. To covert to a
current value, change the Analog Output Select DIP
Switch to 0-20mA. Program with A065 [Analog Out
Sel]. Max analog value can be scaled with A066
[Analog Out High].
Maximum Load:

4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)

A065, A066

17

Opto Output 1

MotorRunning

Program with A058 [Opto Out1 Sel]

A058, A059,
A064

18

Opto Output 2

At Frequency

Program with A061 [Opto Out2 Sel]

A061, A062,
A064

19

RS485 (DSI) Shield –

Terminal should be connected to safety ground - PE
when using the RS485 (DSI) communications port.

(1)

See Footnotes (1) and (4) on page 8.

(2)

0-10V In and 4-20mA In are distinct input channels and may be connected simultaneously.
Inputs may be used independently for speed control or jointly when operating in PID mode.