Setting the term, -bias, and +bias switches, Setting the term, -bias, and – Rockwell Automation 22-COMM-B PowerFlex BACnet MS/TP Adapter User Manual

Page 20

Advertising
background image

2-4

Installing the Adapter

Setting the TERM, -BIAS, and +BIAS Switches

The adapter’s TERM, -BIAS, and +BIAS switches (

Figure 2.2

) are used

to turn on/off its built-in termination resistor and bias resistors.

Figure 2.2 Setting the TERM, -BIAS, and +BIAS Switches

Since nodes on a BACnet MS/TP network are typically a mix of
Allen-Bradley PowerFlex drives and other brands of building automation
products, the network node locations for the PowerFlex drives will
determine how their adapter’s TERM, -BIAS, and +BIAS switches
should be set.

104

0

0

0

1

0

1

1

116

0

0

1

0

1

1

1

105

1

0

0

1

0

1

1

117

1

0

1

0

1

1

1

106

0

1

0

1

0

1

1

118

0

1

1

0

1

1

1

107

1

1

0

1

0

1

1

119

1

1

1

0

1

1

1

108

0

0

1

1

0

1

1

120

0

0

0

1

1

1

1

109

1

0

1

1

0

1

1

121

1

0

0

1

1

1

1

110

0

1

1

1

0

1

1

122

0

1

0

1

1

1

1

111

1

1

1

1

0

1

1

123

1

1

0

1

1

1

1

112

0

0

0

0

1

1

1

124

0

0

1

1

1

1

1

113

1

0

0

0

1

1

1

125

1

0

1

1

1

1

1

114

0

1

0

0

1

1

1

126

0

1

1

1

1

1

1

115

1

1

0

0

1

1

1

127

1

1

1

1

1

1

1

Table 2.A MAC Address Switch Settings (UP = 1 = OPEN) (Continued)

MAC

Address

Switch Setting

MAC

Address

Switch Setting

SW1 SW2 SW3 SW4 SW5 SW6 SW7

SW1 SW2 SW3 SW4 SW5 SW6 SW7

Switches

Description

Default

SW1

Turns on/off the termination resistor

Up (Off)

SW2

Turns on/off the -bias resistor

Up (Off)

SW3

Turns on/off the +bias resistor

Up (Off)

SW4

Reserved (not used)

UP = OFF

TERM Switch (SW1)

-BIAS Switch (SW2)

+BIAS Switch (SW3)

RSRV Switch (SW4)
Reserved for future use

1

4

3

2