Adapter Parameters

B-3

06

[Baud Rate Cfg]

Sets the baud rate (kilobits per second) at which
the adapter communicates. (Updates Parameter
07 - [Baud Rate Act]
after a reset.)

Default:

0 = Autobaud

Values:

0 = Autobaud
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps

Type:

Read/Write

Reset Required:

Yes

07

[Baud Rate Act]

Displays the baud rate (kilobits per second)
actually used by the adapter.

Default:

0 = Unknown

Values:

0 = Unknown
1 = 9600 kbps
2 = 19200 kbps
3 = 38400 kbps
4 = 76800 kbps

Type:

Read Only

08

[MAC Address]

Displays the address set by the MAC Address
Switches SW1…SW7 (

Figure 2.1

) on the adapter.

This value is latched when the adapter powers up.

Default:

0

Minimum:

0

Maximum:

127

Type:

Read Only

09

[Max Master]

Sets the maximum MAC Address for any device in
the BACnet MS/TP token ring.

Default:

127

Minimum:

0

Maximum:

127

Type:

Read/Write

Reset Required:

Yes

10

[Max Info Frames]

Sets the maximum number of messages that the
adapter can transmit while it owns the token.

Default:

1

Minimum:

1

Maximum:

255

Type:

Read/Write

Reset Required:

Yes

11

[Device Inst Hi]

Sets the high portion (most significant digits) of
the Device Instance Number. The Device Instance
Number used by the adapter is the value of this
parameter times 1000 plus the value of Parameter
12 - [Device Inst Lo]
.

Default:

160

Minimum:

0

Maximum:

4194

Type:

Read/Write

Reset Required:

Yes

12

[Device Inst Lo]

Sets the low portion (always the last three least
significant digits) of the Device Instance Number.
The Device Instance Number used by the adapter
is the value of Parameter 11 - [Device Inst Hi]
times 1000 plus the value of this parameter.

Default:

0

Minimum:

0

Maximum:

999

Type:

Read/Write

Reset Required:

Yes

Parameter

No. Name and Description

Details