Configuring the Adapter

3-5

high portion (most significant digits) of the number and Parameter 12 -
[Device Inst Lo]
to enter the low portion (always the three least
significant digits) of the number.

Figure 3.3

illustrates how to apportion

the Device Instance Number for entry into the adapter.

Figure 3.3 Apportioning the Device Instance Number for Entry

1. Enter the Device Instance Number using Parameter 11 - [Device

Inst Hi] and Parameter 12 - [Device Inst Lo].

Figure 3.4 Example Device Inst Hi/Lo HIM Screens

Table 3.B

shows Device Instance Number examples to illustrate the

values needed to be entered for each parameter.

Table 3.B Examples of Device Instance Numbers

2. Reset the adapter (see

Resetting the Adapter on page 3-9

) to apply

the new Device Instance Number.

Device Instance
Number

Parameter 11 -
[Device Inst Hi] Value

Parameter 12 -
[Device Inst Lo] Value

14

0

14

328

0

328

2369

2

369

160000 (default)

160

0

4150732

4150

732

Device Instance Number

Most Significant Digits

Use Parameter 11 - [Device Inst Hi]

to enter value.

Least Significant Digits
Use Parameter 12 - [Device Inst Lo]
to enter value.

Device Inst Hi

Parameter:

#

011

160

VALUE

LIMITS

SEL

Device Inst Lo

Parameter:

#

012

0

VALUE

LIMITS

SEL