Verifying/setting key adapter parameters, Configuring/verifying key drive parameters – Rockwell Automation 22-COMM-B PowerFlex BACnet MS/TP Adapter User Manual

Page 26

Advertising
background image

2-10

Installing the Adapter

Table 2.B Drive and Adapter Start-Up Status Indications

Verifying/Setting Key Adapter Parameters

For instructions to use an optional PowerFlex 4-Class HIM to access
adapter parameters, see

Using the Optional, External PowerFlex 4-Class

HIM on page 3-2

.

1. Verify that adapter Parameter 08 - [MAC Address] is reporting the

MAC address set in

Setting the MAC Address on page 2-2

.

2. Set adapter Parameters 11 - [Device Inst Hi] and 12 - [Device Inst

Lo] to establish a unique number for representation to the Building
Automation Controller. For more information, see

Setting the Device

Instance Number on page 3-4

.

3. Reset the adapter by setting adapter Parameter 01 - [Reset Module]

to “1” (Reset Module) to apply the new Device Instance Number.

Configuring/Verifying Key Drive Parameters

The PowerFlex 4-Class drive can be separately configured for the control
and reference functions in various combinations. For example, you
could set the drive to have its control come from a peripheral or terminal
block with the reference coming from the BACnet MS/TP network. Or
you could set the drive to have its control come from the BACnet MS/TP
network with the reference coming from another peripheral or terminal
block. Or you could set the drive to have both its control and reference
come from the BACnet MS/TP network.

Item Name

Color

State

Description

Drive FAULT Status Indicator

FAULT

Red

Off

Drive ready but not running, and no faults are present.

Flashing

A fault has occurred.

Adapter Status Indicators

PORT

Green

Flashing

Normal Operation. The adapter is establishing
communications with the drive. It will turn solid green or red.

Steady

Normal Operation. The adapter is properly connected and
communicating with the drive

MOD

Green

Flashing

Normal Operation. The adapter is operating but is not
transferring I/O data.

Steady

Normal Operation. The adapter is operating and transmitting
I/O data.

NET A

Green

Flashing

Normal Operation. The adapter is properly connected and
communicating on the network.

NET B

Green

Off

Normal Operation. The adapter is properly connected but is
idle.

Flashing

Normal Operation. The adapter is transmitting data.