3-8
Configuring the Adapter
The value of Parameter 06 - [Baud Rate Cfg] determines the baud rate
used by the adapter. The Autobaud setting will detect the baud rate used
on the network if another device is setting the baud rate. Your application
may require a different setting.
1. Set the value of Parameter 06 - [Baud Rate Cfg] to the baud rate at
which your network is operating.
Figure 3.7 Example Baud Rate Cfg HIM Screen
2. Reset the adapter (see
) so that the new baud
rate takes effect.
Setting the Baud Rate
Value
Description
0
Autobaud (Default)
1
9600
2
19200
3
38400
4
76800
Baud Rate Cfg
Parameter:
#
006
Autobaud
0
VALUE
LIMITS
SEL