Connecting the adapter to the network, Connecting the adapter to the network -3 – Rockwell Automation 20-COMM-S RS-485 DF1 Adapter User Manual
Page 17

Installing the Adapter
2-3
1. Remove power from the drive.
2. Use static control precautions.
3. Connect an RS-485 cable to the network, and route it through the
bottom of the PowerFlex drive.
4. Connect a 6-pin linear plug to the RS-485 cable.
Figure 2.3 Example Network Connections
(1) The shield must be grounded at a single point on the network (jumper terminals
SHIELD and GND).
(2) Jumper Terminals TERM and A on the adapters at end of the RS-485 network. This
enables a built in RC termination network on the adapter.
5. Connect the cable to the adapter.
Connecting the Adapter to the Network
!
ATTENTION: Risk of injury or death exists. The PowerFlex drive
may contain high voltages that can cause injury or death. Remove
power from the drive, and then verify power has been discharged before
installing or removing an adapter.
Terminal
Signal
Function
GND
CHASSIS GND
(1)
Shield GND termination
SHIELD
SHIELD
Shield RC termination
COM
COMMON
Signal Common
B
Signal B
Tx Rx D-
A
Signal A
Tx Rx D+
TERM
TERMINATION
(2)
Signal RC termination
Node 1
Node 2
Node "n"
TERMA
B
COM SHIELD
GND
TERMA
B
COM SHIELD
GND
TERMA
B
COM SHIELD
GND