Installing the Adapter

2-3

1. Remove power from the drive.

2. Use static control precautions.

3. Connect an RS-485 cable to the network, and route it through the

bottom of the PowerFlex drive.

4. Connect a 6-pin linear plug to the RS-485 cable.

Figure 2.3 Example Network Connections

(1) The shield must be grounded at a single point on the network (jumper terminals

SHIELD and GND).

(2) Jumper Terminals TERM and A on the adapters at end of the RS-485 network. This

enables a built in RC termination network on the adapter.

5. Connect the cable to the adapter.

Connecting the Adapter to the Network

!

ATTENTION: Risk of injury or death exists. The PowerFlex drive
may contain high voltages that can cause injury or death. Remove
power from the drive, and then verify power has been discharged before
installing or removing an adapter.

Terminal

Signal

Function

GND

CHASSIS GND

(1)

Shield GND termination

SHIELD

SHIELD

Shield RC termination

COM

COMMON

Signal Common

B

Signal B

Tx Rx D-

A

Signal A

Tx Rx D+

TERM

TERMINATION

(2)

Signal RC termination

Node 1

Node 2

Node "n"

TERMA

B

COM SHIELD

GND

TERMA

B

COM SHIELD

GND

TERMA

B

COM SHIELD

GND