5-8

Troubleshooting

Events

Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel may troubleshoot the problem. The
following events may appear in the event queue:

Code

Event Description

1

No Event

Empty event queue entry.

2

DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be

caused by loose or broken cables or by noise.

3

Ping Time Flt

A ping message was not received on DPI within the specified
time.

4

Port ID Flt

The adapter is not connected to a correct port on a DPI
product.

5

Port Change
Flt

The DPI port changed.

6

Host Sent
Reset

The DPI product issued this because it was reset.

7

EEPROM Sum
Flt

The EEPROM in the adapter is corrupt.

8

Online @
125 kbps

The adapter and DPI product are communicating at 125 kbps.

9

Online @
500 kbps

The adapter and DPI product are communicating at 500 kbps.

10

Bad Host Flt

The adapter was connected to an incompatible product.

11

Dup. Port Flt

Another peripheral with the same port number is already in
use.

12

Type 0 Login

The adapter has logged in for type 0 control.

13

Type 0 Time
Flt

The adapter has not received a type 0 status message within
the specified time.

14

DL Login

The adapter has logged into a Datalink.

15

DL Reject Flt

The Host rejected an attempt to log in to a Datalink because
the Datalink is not supported or is used by another peripheral.

16

DL Time Flt

The adapter has not received a Datalink message within the
specified time.

17

Control
Disabled

The adapter has sent a “Soft Control Disable” command to the
DPI product.

18

Control
Enabled

The adapter has sent a “Soft Control Enable” command to the
DPI product.

19

PCCC IO Time
Flt

The adapter has not received a PCCC control message within
the specified time-out interval.

20

Normal
Startup

The adapter successfully started up.

21

Message
Timeout

A Client-Server message sent by the peripheral was not
completed.