5-2

Troubleshooting

PORT Status Indicator

Status

Cause

Corrective Action

Off

The adapter is not powered or
is not connected properly to
the drive.

• Securely connect the adapter to the drive

using the ribbon cable.

• Apply power to the drive.

Flashing
Red

The adapter is not receiving a
ping message from the drive.

• Verify that cables are securely connected.

• Cycle power to the drive.

Solid
Red

The drive has refused an
I/O connection from the
adapter.

Another DPI peripheral is
using the same DPI port as
the adapter.

Important: Cycle power to the product after
making any of the following corrections.

• Verify that all DPI cables are securely

connected and not damaged. Replace
cables if necessary.

• Verify that the DPI Host supports

Datalinks.

• Configure the adapter to use a Datalink

that is not already being used by another
peripheral.

Orange

The adapter is connected to a
product that does not support
Allen-Bradley DPI
communications.

• Connect the adapter to a product that

supports Allen-Bradley DPI
communications (for example, PowerFlex
drives).

Flashing
Green

The adapter is establishing an
I/O connection to the drive or
Parameter 12 - [DPI I/O
Config]
is configured for all
I/O disabled.

• No Action. This status indicator will turn

solid red.

• Verify Parameter 12 - [DPI I/O Config]

settings.

• Normal behavior if no DPI I/O is enabled.

Solid
Green

The adapter is properly
connected and is
communicating with the drive.

• No Action.