Rockwell Automation 20-COMM-S RS-485 DF1 Adapter User Manual
Page 48

B-4
Adapter Parameters
16
17
18
19
20
21
22
23
[Flt Cfg A1]
[Flt Cfg A2]
[Flt Cfg B1]
[Flt Cfg B2]
[Flt Cfg C1]
[Flt Cfg C2]
[Flt Cfg D1]
[Flt Cfg D2]
Sets the data that is sent to the Datalink in the
drive if the following is true:
• Parameter 10 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important: If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.
24
[CRC/BCC Cfg]
Techniques for error detection in data
communications. Must match the technique used
by the software or controller communicating with
the adapter.
Default:
0 = BCC
Bit Values:
0 = BCC
1 = CRC
Type:
Read/Write
Reset Required:
Yes
25
[CRC/BCC Act]
Actual checksum or CRC selection.
Default:
0 = BCC
Bit Values:
0 = BCC
1 = CRC
Type:
Read Only
26
[Dup Msg Detect]
Determines if the adapter ignores duplicate
messages. Normally set to Enable (default). Set to
Disable if using a ProSoft 3150-DFM module or
any device which does not increment the TNS ID.
Default:
1 = Enable
Bit Values:
0 = Disable
1 = Enable
Type:
Read/Write
Reset Required:
No
Parameter
No. Name and Description
Details