Rs1/df1 error codes – Rockwell Automation 160 RSI SERIAL COMM MODULE User Manual

Page 41

Advertising
background image

Troubleshooting

9–3

Table 9.B (continued)
160 Drive1 Fault Codes

1

Refer to the

160 User Manual for the most current fault code information.

Table 9.C
RS1 Fault Codes

RS1/DF1 Error Codes

The following error codes could be returned over DF1 (with the
Message Command) when accessing the RS1 Module.

Table 9.D
Error Codes

Fault Code Fault Indication

Description

Corrective Action

40

Phase W Fault

Phase to ground fault detected between drive
and motor phase W.

Check wiring between drive and motor. Check motor
for grounded phase.

41

UV Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive
output terminals for a shorted condition.

42

UW Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive
output terminals for a shorted condition.

43

VW Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive
output terminals for a shorted condition.

48

Reprogramming Fault

Occurs when reset defaults is performed.

Clear fault.

49

Zero Overload Fault

Occurs when load requires excessive current at
zero hertz.

Reduce motor load and/or motor dwell time at zero
hertz.

Fault Code Fault Indication

Description

Corrective Action

51

RS1 Module EPROM Fault

Module EPROM has invalid data.

Reset to factory defaults P128 - [Reset RS1].

52

RS1 Lost I/O Connection

Application timed out.

Check master for correct operation (i.e., powered up,
run mode, etc.).

55

Force Fault

P127 - [Force Fault] was set to “1.”

Clear fault.

Message

STS

EXT STS

Problem

Problem

All Messages 10h

N/A

Illegal command or format.

The RS1 does not support this command.

F0h

06h

Address does not point to anything usable.

The address does not exist, or does not point to anything usable
by this command.

F0h

0Ah

Transaction size plus word address is too large. Trying to read/write multiple parameters with one command.

Writing one parameter at a time or reading past end of last
parameter is only supported.

F0h

12h

Invalid parameter or data.

Data out of range.

F0h

1Eh

Data table element protection violation.

Write to Read Only parameter.

F0h

1Fh

Temporary internal problem.

Unable to execute due to temporary internal conditions –
Parameter Read Only when drive is running.

Advertising