RS1 Module Compatibility

The 160-RS1 Module has been tested and found to be compatible
with the following Allen-Bradley products:

MicroLogix 1000

Protocol

Point-to-Point

PCCC Command 0xA1 Protected Type Logical Read with 2 Address Fields

0xA9 Protected Type Logical Write with 2 Address Fields

Hand Shaking

None

Cable

See Chapter 3 for details

Versions

Series D, FRN 1.0 or later

SLC 500

Protocol

Point-to-Point/Multi-Drop Master

PCCC Command 0xA2 Protected Type Logical Read with 3 Address Fields

0xAA Protected Type Logical Write with 3 Address Fields

Hand Shaking

None

Cable

9 Pin - 9 Pin (

see Chapter 3 for details)

Versions

Series B, FRN 7 (OS 4.01) or later

1761-NET-AIC+

Protocol

Multi-Drop

PCCC Command All

(see Chapter 5 for details)

Hand Shaking

None

Cable

9 Pin - 9 Pin

Versions

Series A

PLC-5 Enhanced

Protocol

Point-to-Point/Multi-Drop Master

PCCC Command 0x67

Typed Write (Logical ASCII Addressing only)

0x68

Typed Read (Logical ASCII Addressing only)

Hand Shaking

None

Cable

9 Pin - 25 Pin (

see Chapter 3 for details)

Versions

Series C, FRN E or later

RSLinx™

Protocol

Point-to-Point/Multi-Drop

PCCC Command 0xA1 Protected Type Logical Read with 2 Address Fields

0xA9 Protected Type Logical Write with 2 Address Fields

Hand Shaking

None

Cable

PC Cable (

see Chapter 3 for details)

Versions

1.7.62.00 or later

DriveExplorer

Protocol

Point-to-Point

PCCC Command 0x67

Typed Write (Logical ASCII Addressing only)

0x68

Typed Read (Logical ASCII Addressing only)

Hand Shaking

None

Cable

PC Cable (

see Chapter 3 for details)

Versions

1.01.10 or later

DriveTools32™

Protocol

Point-to-Point

PCCC Command 0x67

Typed Write (Logical ASCII Addressing only)

0x68

Typed Read (Logical ASCII Addressing only)

Hand Shaking

None

Cable

PC Cable (

see Chapter 3 for details)

Versions

2.01 or later