Saving settings, System configuration – Rockwell Automation 825P Modular Protection System Quick Start Guide User Manual

Page 11

Advertising
background image

Quick Start Guide

Allen-Bradley Bulletin 825-P Modular Protection System

11

11

Saving Settings

It is important to note that programmed values become operational only after they
have been saved to memory. The programming system will prompt to save settings
when the user navigates higher up in the programming menu by pressing the ESCape
key. The front panel display is as follows:

Save Changes?
Yes No

To save changes, place the cursor at “Yes” and press the Enter

key.

System
Configuration

The 825-P displays “STATUS FAILURE” on initial start-up and after a hardware
configuration change. The second line of the display identifies the cause of failure; if
more than one configuration change is found, the highest priority error is identified.
To remove the failure, the new system hardware configuration must be manually
accepted. Use the following procedure with the front panel programming keys:

1. Select “Status” from the MAIN menu and press the Enter

key. The front

panel displays the following:

Confirm Hardware
Config (Enter)

2. Press the Enter

key. The front panel displays the following:

Accept Config?
Yes No

3. Position the cursor at “Yes” and press the Enter

key. The 825-P

programming system checks parameter settings to ensure that no
interdependency setting errors exist. If none exist, the front panel displays the
following:

Config Accepted
Enter to Restart