4. Press the Enter

key. The 825-P reboots and the “Enable” LED

illuminates with the following displayed on the front panel.

825-P MODULAR
PROT SYSTEM
If the LCD display COMMFLT WARNING, configuration of the Port 4 is
required. See next section.

IMPORTANT

If the system check finds interdependency setting errors,
the front panel display:

Settings Mismatch

An example of mismatched settings is the correlation
between the Motor FLA and Phase CT Ratio settings.
Review setting values to determine where the mismatch
exists or, if little or no programming has been performed
yet, reset the 825-P relay to factory default values using the
following path:

MAIN > Reboot/Restore > Restore Defaults

The front panel then displays:

Restore Default?
No Yes

Position the cursor at “Yes” and press the Enter

key.

The 825-P relay will reboot at this point.

Return to the first step of the System Configuration
process.