Allen-Bradley Bulletin 825-P Modular Protection System

17

17

To assign functions to the output relays and inputs, use the following path:

MAIN > Set/Show > IO Assign

ATTENTION

!

Protection elements have no effect until they are assigned
to the Trip relay or an auxiliary relay.

TIP

The relay outputs will function as a N.C. contacts when the
relay behavior setting is Fail-Safe (Y), and will function as a
N.O. contacts when the relay behavior setting is Non-Fail-
Safe (N).