Port 4 Settings
The Port 4 settings configure slot C for communications. Factory default settings are
for DeviceNet communications. Use the following path with the front panel
programming keys to access the Port 4 settings:
MAIN > Set/Show > Port > Port 4
The following table provides direction for the proper settings associated with each
communication option.
❶
A 232 setting is possible, although not typical.
Table C: Communication Settings
Setting Prompt
Setting Range
DeviceNet
Modbus
Empty
COMM INTERFACE
❶
232, 485
232
485
232
PROTOCOL
ASC, MOD
MOD
MOD
MOD
SPEED
300 … 38,400 bps
19,200
19,200
19,200
PARITY
O, E, N
N
N
N
MODBUS SLAVE ID
1 … 248
248
1 to 247
1
IMPORTANT
The 825-P displays “COMMFLT Warning” on initial
power-up with factory default settings when the hardware
installed in Slot C is as follows:
- Empty
- Modbus
- DeviceNet, but not powered