Allen-Bradley Bulletin 825-P Modular Protection System

13

13

Port 4 Settings

The Port 4 settings configure slot C for communications. Factory default settings are
for DeviceNet communications. Use the following path with the front panel
programming keys to access the Port 4 settings:

MAIN > Set/Show > Port > Port 4

The following table provides direction for the proper settings associated with each
communication option.

A 232 setting is possible, although not typical.

Table C: Communication Settings

Setting Prompt

Setting Range

DeviceNet

Modbus

Empty

COMM INTERFACE

232, 485

232

485

232

PROTOCOL

ASC, MOD

MOD

MOD

MOD

SPEED

300 … 38,400 bps

19,200

19,200

19,200

PARITY

O, E, N

N

N

N

MODBUS SLAVE ID

1 … 248

248

1 to 247

1

IMPORTANT

The 825-P displays “COMMFLT Warning” on initial
power-up with factory default settings when the hardware
installed in Slot C is as follows:

- Empty

- Modbus

- DeviceNet, but not powered

Advertising