Remove Pod Assembly
From Enclosure

1.

Access the drive enclosure.

2.

Remove the control pod cover.

3.

Disconnect the factory installed internal 24V power supply cable from
P14 located on the fiber interface board.

4.

Disconnect the factory installed inverter fiber-optic cable from the P1
(INV1) fiber-optic transceiver located on the fiber interface board.

T20 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)

No.

Name

Description

Internal 24V Power Connection Two point connector to P14.

Inverter Fiber-optic Connection

Fiber-optic cable to P1 fiber-optic transceiver INV1.