Original instructions – Rockwell Automation 445L Installation and Operating Instructions User Manual
Page 11

Muting Controller Box Installation and Operating Instructions
11
R
Original instructions
Figure 18: Power-up function
The lockout mode may be reset by one of two methods:
• Power down, then Power up. If the fault is still present the module will lockout again.
• A start signal on switch “Reset/Override”
• A start signal on connector “PWR I/O” Pin 4
Assuming the cause of the lockout has been eliminated (from activating the “Reset/Override” switch for ten seconds), the controller starts
up. If the safety light curtain is interrupted, e.g. due a pallet, the controller goes into a safe off mode. The “Reset/Override” switch has to
be reactivated again to start the mute-dependent-override function (see Figure 18).
Figure 19: Muting System
24V
Output
Status
0V
24V
Error
Status
0V
24V
Start
0V
24V
OSSD
0V
> 0.1 s
> 10 sec
Muting Controller Box
(MSR42) (445L-AMUTBOX1)
Floor Mounting Plate
(included with
mounting stand)
Muting Sensor
Cantilever
(445L-AMSTDMUT)
Reflector
Light Curtains—POC or PAC—
(GuardShield Micro 400,
Safe 2, OR Safe 4)
Mounting Stand
(445L-AMSTD2M)