Muting Controller Box Installation and Operating Instructions

21

R

Original instructions

GuardShield Type 2/Type 4 (440L)

Step 4

Mounting of the Muting Sensors

Step 5

Mounting of the Retroreflectors

Muting with GuardShield Micro 400

For muting a GuardShield Micro 400 safety light curtain use the safety software to create a configuration and download it to the MSR42
controller.

Two-Beam or Four-Beam Muting

The MSR42 offers two beam and four beam muting according to the Muting Types section (page 12). The controller box is delivered by
default with the two-beam T-type muting. Other muting configurations can be selected with the safety software and downloaded with
the optical interface.

Note: Four beam muting is only possible if the Micro 400 safety light curtain is used.

The mounting brackets for the GuardShield 440L are supplied with
the light curtain.

T-slot nut and screws are included with the floor mounting column.

Before mounting, check for height and cable exit position (bottom
or top).

Premount the bracket

Premount the light curtain with the supported screws.
Tighten the screws after aligning.

Note: Only one slot of the GuardShield bracket will fit into

the mounting stand channel.

Before starting to mount the muting sensors, check the section for
the mounting position with respect to the muting type. Mount the
muting sensor according its instruction.

T-slot nut and screws for the RightSight bracket 60-2649 are
supported with the cantilever.

Check for good visibility of the sensor indicator LEDs.

Check the Muting Types section on page 12 for the mounting
position for the chosen muting type.

T-slot nut and screws are provided with the cantilever.