Muting Controller Box Installation and Operating Instructions

13

R

Original instructions

L-Type 2 Sensor

Muting Function

Moving goods (e.g. pallet) through the muting station leads to the timing diagram of the left picture below. During the mute time
[t(mute)] the muting lamp is lit. Muting sensor S1 and muting sensor S2 must have a timing delay of at least >50 ms.

Timing for 2 Sensor T-type (standard factory supplied configuration)

h1:

Lowest beam of safety light curtain

Recommended mounting position according to IEC 62046 F.2:

h2:

Muting sensor height

d1 < 200 mm

d1:

Distance light curtain — muting sensor

d2 > 250 mm

d2:

Distance muting sensor — muting sensor

h2

≥ h1

d1

d2

h1

h2

d1

d2

ESPE

Muting Sensor S1

Muting Sensor S2

t SENS

t SENS

t ESPE

t ESPE

t MUTE

Mute

ESPE

Muting Sensor S1

Muting Sensor S2

t SENS

t SENS

t ESPE

t ESPE

t MUTE

Mute