R

SafeZone™ Safety Laser Scanner User Manual

34 10000073050, July 2011

Original instructions

6.1.2 Applications with multiple monitored areas
(SafeZone multizone safety laser scanner)

Figure 54: Hazardous area protection with SafeZone multizone
safety laser scanner

The two areas to be monitored are switched using the static control
inputs depending on the phase of the process on the machine. For
example the area

Œ or the area  can be monitored, both areas can be

monitored or none.

Figure 55: Access protection with SafeZone multizone safety laser
scanner

The two areas to be monitored are switched using the static control
inputs depending on the process phase. For example the area

Πor the

area

 can be monitored, both areas can be monitored or none. For

safety against manipulation on the SafeZone multizone safety laser
scanner, e.g. the floor is used as a reference in each case. If the position of
the SafeZone multizone safety laser scanner changes (e.g. due to change
to the mounting), the SafeZone multizone safety laser scanner shuts
down.

6.2 Mobile applications

6.2.1 Vehicle monitoring for unidirectional travel
(SafeZone safety laser scanner)

Figure 56: Vehicle monitoring with SafeZone safety laser scanner

The SafeZone safety laser scanner monitors the area in one direction of
travel and stops the vehicle as soon as there is an object in the protective
safety field.

6.3 Example circuits

Sketch key
• 1) = output circuits

These contacts are to be connected to the controller such that, with the
output circuit open, the dangerous state is disabled. For categories 3 and
4 in compliance with EN 954-1, the interfacing must be two-channel (x-
/y paths). Observe the maximum values for the loading of the outputs
(see Section 11.4 “Data sheet” on page 45).

• H2 = indication for error/contamination

• H3 = indication for waiting for restart

• H8 = indication for warning field interruption

SafeZone multizone with two

protective safety fields and

warning fields — mounted

horizontally

SafeZone multizone with two

protective safety fields —

mounted vertically

Floor as reference

2

1

IMPORTANT

Only use relays with positively-driven
contacts. The protection elements
connected in parallel with the
contactors are used for arc-
suppression.

Ensure that there is adequate arc-
suppression at the relay contacts. Take
into account that arc-suppressors may
lengthen the response time.

SafeZone multizone with
protective safety field and
warning field