Minimum

Typical

Maximum

Electrical Data

Electrical connection

Plug-in connection housing with screw terminal connections

Technical data, screw terminals

Cross-section of rigid cores

0.14 mm

2

1.5 mm

2

Cross-section of flexible cores

Ž

0.14 mm

2

1.0 mm

2

American Wire Gauge (AWG)

26

16

Insulation stripping length for the cores

5 mm

Screw tightening torque

0.22 nm

0.25 nm

Cable length for power supply tolerance ±10%

For cable cross-section 1 mm

2

50 m

For cable cross-section 0.5 mm

2

25 m

For cable cross-section 0.25 mm

2

12 m

Cable length for power supply tolerance ±5%

For cable cross-section 1 mm

2

60 m

For cable cross-section 0.5 mm

2

30 m

For cable cross-section 0.25 mm

2

15 m

Cable length for power supply tolerance ±1%

For cable cross-section 1 mm

2

70 m

For cable cross-section 0.5 mm

2

35 m

For cable cross-section 0.25 mm

2

17 m

Supply voltage (SELV)
The voltage supply must be capable of buffering brief mains voltage failures of 20 ms as specified in EN 60 204.
Suitable power supplies are available from Rockwell Automation
Automation

16.8V

24V

28.8V

Permissible residual ripple



±5%

Switch on current



2 A

Operating current at 24 V without output load

0.8 A

Operating current with max. output load

2.3 A

Power consumption without output load

19 W

Power consumption with maximum output load

55 W

Input for control switch for restarting or resetting

Input resistance when HIGH

2 k

Ω

Voltage for HIGH

11V

24V

28.8V

Voltage for LOW

-3V

0V

5V

Input capacitance

15 nF

Static input current

6 mA

15 mA

Input EDM

Input resistance when HIGH

2 k

Ω

Voltage for HIGH

11V

24V

28.8V

Voltage for LOW

-3V

0V

5V

Input capacitance

15 nF

Static input current

6 mA

15 mA

Advertising